실규모의 고도처리공정에서 NADH변화 유형과 이를 활용한 공정제어

이용수 6

영문명
NADH Variation and Process Control with NADH Fluorometer in Full Scale Biological Nutrient Removal Process
발행기관
한국환경보건학회
저자명
김한래 조종복 조일형(cho ih hyoung) 이진우 장순웅(CHANG SOON WOONG) 이시진(Si-Jin Lee)
간행물 정보
『1. 한국환경보건학회지』제34권 제6호, 423~432쪽, 전체 10쪽
주제분류
공학 > 환경공학
파일형태
PDF
발행일자
2008.12.30
4,000

구매일시로부터 72시간 이내에 다운로드 가능합니다.
이 학술논문 정보는 (주)교보문고와 각 발행기관 사이에 저작물 이용 계약이 체결된 것으로, 교보문고를 통해 제공되고 있습니다.

1:1 문의
논문 표지

국문 초록

영문 초록

In this study, we investigated the possibility of auto control and the proper operating factors in the BNR(Biological Nutrient Removal) process using an NADH(Reduced Nicotinamide Adenine Dinucleotide) fluorometer, which characterized the emitted fluorescence when activated by flashes of UV light at 460 nm. In terms of finding adequate operating parameters, results indicted that nitrification efficiency decreased in the controlled DO while denitrification efficiency decreased in the controlled pH. The above results indicated that controlled operating condition after combination with NADH, DO and pH was resonable. Result obtained from the correlation between NADH and pH showed that variation trend of influent loading was similar to those of NADH and pH, and also the variation cycle was repeated on a daily basis. Consequently, this result showed the increase of BOD loading caused the nitrification efficiency to decrease because air-flow, required for nitrification, was reduced, and so the NADH value was increased. From these results, it is possible to use NADH flourimetry to assess the variation of organic load and nitrification efficiency in the case of small change in influent pH such as in sewage and also to handle and operate the load variation in the auto control system using the NADH fluorometer. In this study, we investigated the possibility of auto control and the proper operating factors in the BNR(Biological Nutrient Removal) process using an NADH(Reduced Nicotinamide Adenine Dinucleotide) fluorometer, which characterized the emitted fluorescence when activated by flashes of UV light at 460 nm. In terms of finding adequate operating parameters, results indicted that nitrification efficiency decreased in the controlled DO while denitrification efficiency decreased in the controlled pH. The above results indicated that controlled operating condition after combination with NADH, DO and pH was resonable. Result obtained from the correlation between NADH and pH showed that variation trend of influent loading was similar to those of NADH and pH, and also the variation cycle was repeated on a daily basis. Consequently, this result showed the increase of BOD loading caused the nitrification efficiency to decrease because air-flow, required for nitrification, was reduced, and so the NADH value was increased. From these results, it is possible to use NADH flourimetry to assess the variation of organic load and nitrification efficiency in the case of small change in influent pH such as in sewage and also to handle and operate the load variation in the auto control system using the NADH fluorometer.

목차

키워드

해당간행물 수록 논문

참고문헌

교보eBook 첫 방문을 환영 합니다!

신규가입 혜택 지급이 완료 되었습니다.

바로 사용 가능한 교보e캐시 1,000원 (유효기간 7일)
지금 바로 교보eBook의 다양한 콘텐츠를 이용해 보세요!

교보e캐시 1,000원
TOP
인용하기
APA

김한래, 조종복, 조일형(cho ih hyoung), 이진우, 장순웅(CHANG SOON WOONG), 이시진(Si-Jin Lee). (2008).실규모의 고도처리공정에서 NADH변화 유형과 이를 활용한 공정제어. 1. 한국환경보건학회지, 34 (6), 423-432

MLA

김한래, 조종복, 조일형(cho ih hyoung), 이진우, 장순웅(CHANG SOON WOONG), 이시진(Si-Jin Lee). "실규모의 고도처리공정에서 NADH변화 유형과 이를 활용한 공정제어." 1. 한국환경보건학회지, 34.6(2008): 423-432

결제완료
e캐시 원 결제 계속 하시겠습니까?
교보 e캐시 간편 결제