학술논문
농촌지역 오수처리시설의 성능평가 몇 개선방안
이용수 9
- 영문명
- Performance Evaluation and Improvement of Sewage Treatment Facility in Rural Area
- 발행기관
- 대전대학교 환경문제연구소
- 저자명
- 박충환(Chung-Hwan Park) 박희동(Hee-Oong Park) 이창균(Chang-Kyun Lee) 임봉수(Bong-Su Lim)
- 간행물 정보
- 『環境問題硏究所 論文集』第6號, 19~28쪽, 전체 10쪽
- 주제분류
- 공학 > 환경공학
- 파일형태
- 발행일자
- 2002.02.28
4,000원
구매일시로부터 72시간 이내에 다운로드 가능합니다.
이 학술논문 정보는 (주)교보문고와 각 발행기관 사이에 저작물 이용 계약이 체결된 것으로, 교보문고를 통해 제공되고 있습니다.
국문 초록
영문 초록
This study was carried out to evaluate performance of sewage treatment facility in rural area. Average effluent concentration was 7.6mg/l BOD, 10.3mg/l COD. 4.7mg/l SS, 19.140mg/l TN. and 1.631mg/l TP. within discharge quality standard. The removal efficiency rate of BOD. COD and SS was good as 89.8%. 78.5% and 90.1 %. respectively. But that of TN. TP was very low as 25.0% and 31.4% respectvely. Average sewage flow rate was investigated by about 1.1㎥/d per household. 398 I pcd. In rainfall period. the removal efficiency rate of BOD. TN and TP was very low as 15%. 22% and 28%. respectively because of inflow and infiltration into sewer. In flowing concentration of sewage was diluted as rain is inserted into sewer and submerged facility was not operated at normal condition. Therefore it is required that the sewer will have to repair and hydraulic design for facility will have to be check. So it is necessary to support systematical. administrative measures for responsible management.
목차
ABSTRACT
1. 서론
2. 조사대상 및 방법
3. 결과 및 고찰
4. 결론
참고문헌
키워드
해당간행물 수록 논문
참고문헌
관련논문
공학 > 환경공학분야 BEST
더보기공학 > 환경공학분야 NEW
- 도심환경교통(Urban Air Mobility, UAM) 도입에 따른 소음 문제에 대한 시론 -UAM 소음의 특성과 잠재적 건강영향: 연구 방향 및 관리를 위한 정책적 고려사항-
- 광주지역 공공수역의 미생물 군집 다양성 및 항생제 내성에 관한 연구
- 서울시 관악구 도림천 복개 정도에 따른 환경 악취 요인 분석
최근 이용한 논문
교보eBook 첫 방문을 환영 합니다!
신규가입 혜택 지급이 완료 되었습니다.
바로 사용 가능한 교보e캐시 1,000원 (유효기간 7일)
지금 바로 교보eBook의 다양한 콘텐츠를 이용해 보세요!